Trailing cable FABER® (N)3GHSSYCY
Trailing cable FABER® (N)3GHSSYCY
Использование
As power supply cable for mobile MV equipment in mining and tunnel applications.
Конструкция
| Customs Tariff Number (code number) |
85446010900000000
|
| Standard |
VDE 0250-605 (with ref. to)
|
| Conductor material |
copper, bare
|
| Conductor construction |
Class 5 = flexible
|
| Insulation |
basic EPR
|
| Electrical field control |
inner and outer semiconducting rubber layer
|
| Pilot conductor |
split in the outer interstices
|
| Arrangement of protective conductors |
copper wires on each core
|
| Monitoring core |
copper wire spinning on first inner sheath
|
| Armour |
steel wire braid, galvanized
|
| Sheathing material |
PVC DMV6
|
| Colour of outer sheath |
red
|
| Flame-retardant |
VDE 0482-332-1-2/IEC 60332-1-2
|
| UV-resistant |
yes
|
| Max. temperature at conductor, °C |
90 °C
|
| Max. short circuit temperature at conductor, °C |
250 °C
|
| Permitted outer cable temperature, fixed, °C |
-40 - +80 °C
|
| Permitted outer cable temperature, moved, °C |
-25 - +80 °C
|
| Bending radius, fixed installation |
6 x Ø
|
| Min. distance with S-type diretional changes |
20 x Ø
|
| Bending radius, moving application |
10 x Ø
|
| Maximum tensile strength at the conductor |
15 N/mm²
|
| Number of cores |
3
|
| metal base Cu |
150 EUR/100 kg
|
| Unit of measurement |
metre
|
Стандарты
As power supply cable for mobile MV equipment in mining and tunnel applications.
| Артикул |
Типоразмер кабеля |
| 054666 |
FABER (N)3GHSSYCY 3X35+3X16/3E+3X2.5+UEL 20KV RD |
| 054835 |
FABER (N)3GHSSYCY 3X50+3X25/3E+3X2.5+UEL 20KV RD |
| 054836 |
FABER (N)3GHSSYCY 3X95+3X50/3E+3X2.5+UEL 20KV RD |
| 054916 |
FABER (N)3GHSSYCY 3X25+3X16/3E+3X2.5+UEL 10KV RD |
| 054917 |
FABER (N)3GHSSYCY 3X25+3X16/3E+3X2.5+UEL 20KV RD |
| 054929 |
FABER (N)3GHSSYCY 3X35+3X16/3E+3X2.5+UEL 10KV RT |
| 054930 |
FABER (N)3GHSSYCY 3X50+3X25/3E+3X2,5+UEL 10KV RT |