RE-2X(St)YSWAY-fl PiMF
Instrumentation cable RE-2X(St)YSWAY-fl [PiMF]
Использование
For data communication with transmission rates up to 200 kBit/s in MSR- and EDP systems. Transmission characteristics are guaranteed by high-quality stranding and screening. For fixed installation in dry and damp areas, outdoors and direct burial in earth.The types with blue outer sheath are suitable for intrinsically safe installation -Ex i- in hazardous areas. Core identification: black-white(-orange) with sequential numbering
Конструкция
| Customs Tariff Number (code number) |
85444995900000000
|
| Standard |
EN 50288-7 (with ref. to)
|
| Conductor material |
copper, bare
|
| Conductor construction |
class 2, 7-wired construction
|
| Insulation |
XLPE
|
| Stranding unit |
Pair
|
| Stranding |
Layers
|
| Core wrapping |
plastic foil
|
| Material inner sheath |
PVC
|
| Screen |
plastic coated Al-foil + copper drain wire, tinned
|
| Armour |
round steel wire, galvanized
|
| Sheathing material |
PVC
|
| Flame-retardant |
VDE 0482-266-2-4/IEC 60332-3-24 (Cat. C)
|
| UV-resistant |
yes
|
| Oil-resistant |
yes
|
| For outdoor use |
yes
|
| Permitted outer cable temperature, fixed, °C |
-30 - +70 °C
|
| Permitted outer cable temperature, moved, °C |
-5 - +50 °C
|
| Bending radius, fixed installation |
12 x Ø
|
| Insulation resistance |
1000 MOhmxkm
|
| Core identification |
black/white with numbers
|
| Nominal cross section, sqmm |
1.3 mm²
|
| Conductor resistance |
14.2 Ohm/km
|
| metal base Cu |
100 EUR/100 kg
|
| Unit of measurement |
metre
|
Стандарты
For data communication with transmission rates up to 200 kBit/s in MSR- and EDP systems. Transmission characteristics are guaranteed by high-quality stranding and screening. For fixed installation in dry and damp areas, outdoors and direct burial in earth.The types with blue outer sheath are suitable for intrinsically safe installation -Ex i- in hazardous areas. Core identification: black-white(-orange) with sequential numbering
| Артикул |
Типоразмер кабеля |
| 101073 |
RE-2X(St)YSWAY-fl 1X2X1.3 BK IEC 332-3-24 |
| 101151 |
RE-2X(St)YSWAY-fl 1X2X1.3 BU IEC 332-3-24 |
| 101158 |
RE-2X(St)YSWAY-fl PiMF 2X2X1.3 BK IEC 332-3-24 |
| 101159 |
RE-2X(St)YSWAY-fl PiMF 2X2X1.3 BU IEC 332-3-24 |
| 101273 |
RE-2X(St)YSWAY-fl PiMF 4X2X1.3 BK IEC 332-3-24 |
| 101274 |
RE-2X(St)YSWAY-fl PiMF 4X2X1.3 BU IEC 332-3-24 |