PUR insulated cable S07BQ-F
PUR insulated cable S07BQ-F
Использование
In dry and wet environments as well as temporary outdoors under medium mechanical stress. For connection of electrical tools on building sites or in cold environments. The cable is highly oil-, abrasion- and impact resistant.
Конструкция
| Customs Tariff Number (code number) |
85444995900000000
|
| Standard |
DIN EN 50525-2-21 (VDE 0285-525-2-21)
|
| Conductor material |
copper, bare
|
| Conductor construction |
Class 5 = flexible
|
| Insulation |
rubber EI7
|
| Material inner sheath |
elastomer
|
| Sheathing material |
polyurethan
|
| Colour of outer sheath |
black
|
| Flame-retardant |
EN 60332-1-2
|
| UV-resistant |
yes
|
| Max. temperature at conductor, °C |
90 °C
|
| Max. short circuit temperature at conductor, °C |
250 °C
|
| Permitted outer cable temperature, fixed, °C |
-40 - +80 °C
|
| Permitted outer cable temperature, moved, °C |
-25 - +80 °C
|
| Bending radius, fixed installation |
4 x Ø
|
| Bending radius, moving application |
12 x Ø
|
| Nominal voltage Uo |
450 V
|
| Nominal voltage U |
750 V
|
| Core identification |
green-yellow + numbers
|
| Number of cores |
36
|
| diameter conductor |
0.26 mm
|
| Nominal cross section, sqmm |
2.5 mm²
|
| Conductor resistance |
7.98 Ohm/km
|
| Insulation wall thickness |
0.9 mm
|
| Ampacity in air (30 °C) |
27 A
|
| Wall thickness of sheath |
2.6 mm
|
| outer diameter approx. |
41.80 mm
|
| Copper weight (GER) |
864
|
| metal base Cu |
150 EUR/100 kg
|
| net weight per 1000 |
1800 kg
|
| Unit of measurement |
metre
|
Стандарты
In dry and wet environments as well as temporary outdoors under medium mechanical stress. For connection of electrical tools on building sites or in cold environments. The cable is highly oil-, abrasion- and impact resistant.
| Артикул |
Типоразмер кабеля |
| 053444 |
S07BQ-F 36G2.5 UV resistant BK |