(N)TMCGCWOEU
Flexible medium voltage cable (N)TMCGCWOEU
Использование
Single core cables are used in short lengths, e.g. for the connection of switchgear cubicles and for the connection of mobile transformer substations. When laying and during operation, care should be taken to protect them from excessive mechanical stress. The outer semi-conducting layer must not be heated before removal.
Конструкция
| Customs Tariff Number (code number) |
85446010900000000
|
| Standard |
DIN VDE 0250-813 (with ref. to)
|
| Conductor material |
tinned copper
|
| Conductor construction |
Class 5 = flexible
|
| Insulation |
rubber 3GI3
|
| Electrical field control |
inner and outer semiconducting rubber layer
|
| Arrangement of protective conductors |
copper spiral shield
|
| Sheathing material |
rubber (CR) 5GM5
|
| Colour of outer sheath |
red
|
| Flame-retardant |
VDE 0482-332-1-2/IEC 60332-1-2
|
| UV-resistant |
yes
|
| Oil-resistant |
EN 60811-404
|
| Ozone-resistant |
yes
|
| For outdoor use |
yes
|
| Max. temperature at conductor, °C |
90 °C
|
| Max. short circuit temperature at conductor, °C |
250 °C
|
| Permitted outer cable temperature, fixed, °C |
-40 - +80 °C
|
| Permitted outer cable temperature, moved, °C |
-25 - +60 °C
|
| Bending radius, fixed installation |
6 x Ø
|
| Bending radius, moving application |
10 x Ø
|
| Core diameter |
10.1 mm
|
| Number of cores |
1
|
| metal base Cu |
150 EUR/100 kg
|
| Unit of measurement |
metre
|
Стандарты
Single core cables are used in short lengths, e.g. for the connection of switchgear cubicles and for the connection of mobile transformer substations. When laying and during operation, care should be taken to protect them from excessive mechanical stress. The outer semi-conducting layer must not be heated before removal.
| Артикул |
Типоразмер кабеля |
| 051052 |
1X95/16 KON 6/10 kV RD |
| 051103 |
1X300 6/10 kV RD |
| 051169 |
1X240 6/10 kV RD |
| 051268 |
1X240/25 KON 6/10 kV RD |
| 051277 |
1X50/16 KON 12/20 kV RD |
| 051286 |
1X120/16 KON 6/10 kV RD |
| 051302 |
1X185/25 KON 6/10 kV RD |
| 051346 |
1X150/25 KON 6/10 kV RD |
| 051491 |
1X300/25 KON 6/10 kV RD |
| 051542 |
1X300/25 KON 18/30 kV RD |
| 051635 |
1X240/25 KON 18/30 kV RD |
| 051674 |
1X150/25 KON 18/30 kV RD |
| 051740 |
1X95/16 KON 18/30 kV RD |
| 051741 |
1X120/16 KON 18/30 kV RD |
| 051747 |
1X25/16 KON 12/20 kV RD |
| 052574 |
1X35/16 KON 18/30 kV RD |
| 052962 |
1X185/25 KON 18/30 kV RD |
| 053072 |
1X500/35 KON 18/30 kV RD |
| 053134 |
1X400/35 KON 8.7/15 kV RD |
| 053382 |
1X630/35 KON 6/10 kV RD |