(N)3GHSSYCY
Trailing cable (N)3GHSSYCY
Использование
Flexible cable for energy supply of MV equipment, in tunnelling and underground mining applications, according to VDE 0250 Part 605 Standard, as far as applicable.
Конструкция
| Customs Tariff Number (code number) |
85446010900000000
|
| Specification/Standard |
in Anl. VDE 0250 Teil 605
|
| Conductor material |
copper, bare
|
| Conductor construction |
Class 5 = flexible
|
| Insulation |
rubber 3GI3
|
| Electrical field control |
inner and outer semiconducting rubber layer
|
| Central filler |
semiconductive compound on polyester support
|
| Core wrapping |
plastic foil
|
| Arrangement of protective conductors |
copper wires on each core
|
| Monitoring core |
copper wire spinning on first inner sheath
|
| Armour |
steel wire braid, galvanized
|
| Sheathing material |
PVC DMV6
|
| Colour of outer sheath |
red
|
| Flame-retardant |
VDE 0482-332-1-2/IEC 60332-1-2
|
| UV-resistant |
yes
|
| Max. temperature at conductor, °C |
90 °C
|
| Permitted outer cable temperature, fixed, °C |
-40 - +80 °C
|
| Permitted outer cable temperature, moved, °C |
-5 - +80 °C
|
| Number of cores |
3
|
| metal base Cu |
150 EUR/100 kg
|
| Unit of measurement |
metre
|
Стандарты
Flexible cable for energy supply of MV equipment, in tunnelling and underground mining applications, according to VDE 0250 Part 605 Standard, as far as applicable.
| Артикул |
Типоразмер кабеля |
| 051347 |
3X35 + 3X25/3E + 3X2.5 + UEL KON 3.6/6 kV RD |
| 051348 |
3X50 + 3X25/3E + 3X2.5 + UEL KON 3.6/6 kV RD |
| 051603 |
3X35 + 3X16/3E + 3X2.5 + UEL KON 6/10 kV RD |
| 051650 |
3X35 + 3X16/3E + 3X2.5 + UEL KON 12/20 kV RD |
| 051677 |
3X50 + 3X25/3E + 3X2.5 + UEL KON 6/10 kV RD |
| 051684 |
3X95 + 3X50/3E + 3X2.5 + UEL KON 12/20 kV RD |
| 051685 |
3X120 + 3X70/3E + 3X2.5 + UEL KON 12/20 kV RD |
| 051839 |
3X25 + 3X25/3E + 3X2.5 + UEL KON 12/20 kV RD |
| 051840 |
3X35 + 3X25/3E + 3X2.5 + UEL KON 12/20 kV RD |