EIB/KNX PE
Bus cable EIB/KNX PE
Использование
Due to the increased test voltage and the special marking the cable is designed as bus cable in the EIB/KNX facility control system according to EN 50090. For the Instabus itself is used only the red/black pair (transmission of 24 V supply voltage plus data packages), the second pair (white/yellow) is redundant.The cable may be installed on or under plaster, in ducts and buried in the ground.
Конструкция
| Customs Tariff Number (code number) |
85444991000000000
|
| Conductor material |
copper, bare
|
| Conductor construction |
Class 1 = solid
|
| Insulation |
polyethylene
|
| Stranding unit |
Pair
|
| Stranding |
Layers
|
| Screen |
plastic coated aluminium foil + solid copper drain wire
|
| Sheathing material |
polyethylene
|
| Colour of outer sheath |
black
|
| UV-resistant |
yes
|
| Permitted outer cable temperature, fixed, °C |
-30 - +70 °C
|
| Permitted outer cable temperature, moved, °C |
-5 - +50 °C
|
| Bending radius, fixed installation |
7.5 x Ø
|
| Insulation resistance |
100 MOhmxkm
|
| Number of cores |
4
|
| Loop resistance |
73.2 Ohm/km
|
| outer diameter approx. |
8.00 mm
|
| Copper weight (GER) |
21
|
| metal base Cu |
100 EUR/100 kg
|
| net weight per 1000 |
75 kg
|
| Unit of measurement |
metre
|
Стандарты
Due to the increased test voltage and the special marking the cable is designed as bus cable in the EIB/KNX facility control system according to EN 50090. For the Instabus itself is used only the red/black pair (transmission of 24 V supply voltage plus data packages), the second pair (white/yellow) is redundant.The cable may be installed on or under plaster, in ducts and buried in the ground.
| Артикул |
Типоразмер кабеля |
| 101639 |
FaberВ® EIB-bus cable burial 2X2X0.8 BK |